• Skip to primary navigation
  • Skip to main content
  • Skip to primary sidebar
  • Skip to footer
One Step Off The Grid

One Step Off The Grid

Solar, storage and distributed energy news

  • Solar
  • Battery/Storage
  • Off-Grid
  • Efficiency
  • Software
  • Podcasts
  • Tariffs
  • Electric Vehicles
  • Electrification

Does the switch to an induction cooktop mean expensive electric wiring upgrades?

August 15, 2023 by Ben Elliston Leave a Comment

Image: Siemens

You don’t have to go far to find a layperson, salesperson, or even sometimes an electrician who will tell you that an induction cooktop will need a new 32 amp circuit and maybe even a three-phase upgrade as part of its installation.

Online forums are full of people repeating this, and it may be putting people off moving to induction cooking. What is contained in this article may be news to many consumers, but it should not be news to electricians.

By sizing the circuit for a new induction cooktop correctly, it may be possible to re-use an existing circuit in your kitchen without any upgrading. If a gas cooktop is being replaced with an induction cooktop, a new circuit will of course be required, but it may be possible to use smaller gauge cable which is cheaper and easier to work with.

Cooktop load diversity

Going back to the earliest edition of the wiring rules I could find, Australian Standard 3000 (AS3000) has since at least 1976 included a recommended maximum demand for cooktops (or, as they were referred to back then, “hotplates”).

These recommendations appear in Table C5. While not mandatory, this table can used for sizing the cables and circuit breaker for the cooktop circuit. The maximum demand for the appliance is calculated by considering what is known as “load diversity”.

In plain English, this means that a cooktop having a number of different cooking elements and a range of power levels will almost never have all of the elements operating at full power (which is the full-load rating).

In practice, you might use one element on full power and a couple of others on lower settings, or you might have all elements running but at varied power levels.

Consequently, it is possible to economise on cabling by using the assessed maximum demand figures from Table C5.

It should be emphasised that it’s not technically wrong to install cabling to cover the full-load rating of the cooktop, but it’s more expensive and largely unnecessary.

What happens, then, if the circuit is installed according to the Table C5 recommendations and you then use all of your cooktop elements at maximum power?

The circuit breaker will trip to protect the wiring, but circuit breakers don’t trip exactly at their rated current. They permit moderate overloading for a short time before eventually tripping (and will trip faster for larger overloads).

For example, if the cooktop runs at 1.45 times the rating of the circuit breaker, the circuit breaker will trip after one hour. Most meals are prepared in less time than this and without maximum power for the full duration.

Induction cooktops

An induction cooktop usually has between two and five zones with different maximum power ratings. Some zones are bridged together so that the power is shared between the zones. Other zones may have a “boost” function that gives more than the maximum power for a short time.

Even the manufacturers understand that running all zones at full power is very uncommon, which is why features like bridged zones exist.

The specifications for any induction cooktop will include a “connected load” figure in watts (or kilowatts). It can be a bit confusing to find that the total power of all of the zones exceeds the connected load figure in the specifications.

This is because an induction cooktop manages the power internally to never exceed the connected load figure. If you look at the specifications for a cheaper, solid element electric cooktop, you are more likely to find that the sum of the power ratings for all of the elements will equal the connected load figure as there is nothing clever going on.

By way of example, let’s pick two induction cooktops on the market and take a closer look.

Example 1: IKEA VÄLBILDAD

This two-zone IKEA cooktop has a boost function for both zones, but the boost can only be used on one zone at a time.

Total connected load according to the manual: 3700 W

At 230V, this cooktop pulls about 16 amp (3700W divided by 230V). According to Table C5, the assessed maximum demand of this cooktop (that is, for anything less than 5000 W) is also 16 amp. So in this case, the assessed maximum demand is the same as the full-load rating due to the small size of the cooktop. This makes sense – you are very likely to use both zones on this cooktop at the same time.

Example 2: Bosch PVS875FB5E 80cm Serie 6 Induction Cooktop

According to the specifications, this Bosch cooktop has a connected load of 7.4 kW.

The Bosch cooktop pulls a maximum of 32 amp (7400 W divided by 230V). According to Table C5, though, the full-load rating of this appliance lies between 5 kW and 8 kW, so it has an assessed maximum demand of 20 amp – a 40% reduction. This means that an existing circuit might be available to be re-used, saving considerable installation cost.

Conclusion

This article has not discussed the requirement (or lack thereof) for a 3-phase supply. This topic was well covered in an AFR article in April by Tristan Edis (subscription required). This is a great read if you’re interested in avoiding unnecessary 3-phase upgrades.

Hopefully this helps explain the installation requirements for any induction cooktop you’re considering. If you suspect your cooktop is triggering an expensive installation, ask your electrician if they are following Table C5. After all, cooktop diversity has only been in the standard for 50 years!

Ben Elliston undertook step-by-step electrification of his house between 2007 and 2017 and was  delighted when Jemena capped off his gas line. He thanks electricians Mark Hemmingsen and Ben Murphy for reviewing this article.

For more explainers and podcasts about home electrification, visit RenewEconomy’s SwitchedOn.

Filed Under: Electrification

Primary Sidebar

Sign up for our weekly newsletter

Emissions Counter

Renew Economy

RSS Energy News from Renew Economy

  • Tindo signs five-year deal to export Australian made solar panels to Vietnam
  • Neoen starts powering up its second-largest solar farm in Australia
  • I’ve seen the energy future and it’s in China, and Australia must ditch its distrust and collaborate
  • Utilities want control of consumer solar and batteries to help reverse price spikes they just engineered
  • We need more batteries: Spain turns to new technologies after thermal plants fail in blackout

RSS Electric Vehicle News from The Driven

  • The gaping cybersecurity hole in non-Tesla public EV charging facilities
  • The city betting big on wireless charging for electric taxis and last mile deliveries
  • Two “social leasing” programs for zero-emission vehicles  that actually work
  • Nissan launches next generation Leaf, with more range, a new plug, and V2L
  • Mitsubishi to trial battery swap technology for electric trucks and buses

Press Releases

  • Huge luxury Saudi resort goes 100pct renewables with one of world’s biggest batteries
  • How solar + storage can be a game-changer for people with disabilities

Footer

Technologies

  • Solar
  • Battery/Storage
  • Electric Vehicles
  • Energy Efficiency
  • Software/Gadgets
  • Other Renewables
  • Policy
  • Tariffs
  • Contact
  • Advertise with us
  • About One Step Off The Grid
  • Terms of Use
  • Privacy Policy

Copyright © 2025 · OneStep Genesis on Genesis Framework · WordPress · Log in